3.4.9
Rosemount 5900S in a F
OUNDATION
™
Fieldbus system
The Rosemount 5900S Radar Level Gauge supports the F
OUNDATION
Fieldbus (FF)
technology and lets you integrate it into an existing FF network. As long as the power
supply meets certain requirements (see
) the Rosemount
5900S
will be able to operate as any other FF device.
Figure 3-21: Example of an I.S. F
OUNDATION
Fieldbus System
$
%
&
'
(
)
A. I.S. Power Supply
B. Trunk
C. Rosemount 2230 Display
D. Segment Coupler
E. Rosemount 644 Temperature Transmitter
F. Rosemount 5900S Radar Level Gauge
Ensure that the power supply is able to provide the total current needed for all the
connected devices. See
and
for further information.
Ensure that:
•
the Rosemount 5900S and other devices connected to the F
OUNDATION
Fieldbus (FF)
system are compliant with the FISCO or Entity parameters of the power supply.
•
the short circuit protection of the Segment Coupler
consumption of the connected devices.
(7)
See
for Rosemount 5900S approval information
(8)
See the Rosemount 2410 Reference Manual (Document No. 300530EN) for more information on the Segment Coupler.
Installation
Reference Manual
September 2019
00809-0100-5900
82
Reference Manual
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...