5. Repeat for each device to be programmed. Use the
Remove
button if you wish to
change the list of devices to be programmed.
6. Click the
Browse
button to locate the flash program file. File extension *.cry is used
for these files.
7. Click the
Start Programming
button.
Now the
Start Device Programming
window appears.
8. Click the
Start Programming
button to activate device programming.
If a Rosemount 2460 System Hub is used, a maximum of 25 devices can be
programmed. If there are more devices the programming must be divided in two
steps.
9. Update the TankMaster installation by adding new *.ini files for the Rosemount
5900S gauge to the TankMaster installation folder:
Two *.ini files are used for the Rosemount 5900S, RLG.ini and RLG0xx.ini, where xx
is the identification code of the application software.
a) Copy the RLG.ini file to the
C:\Program Files\Rosemount\Server
folder.
b) Copy the RLG0xx.ini file to the
C:\Program Files\Rosemount\Shared
folder
.
Reference Manual
Service and troubleshooting
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
195
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...