11. Select the
Gas Correction
tab.
12. Choose correction method
Air Correction
. This setting is used during the Pin
Verification procedure. When the LPG Setup is finished, and the tank is ready to be
put into operation, the correction method must be set to correspond with the type
of product in the tank.
F
OUNDATION
Fieldbus parameters:
TRANSDUCER 1500>LPG_CORRECTION_METHOD
13. Calibrate. Check the distance to the calibration ring at the end of the still-pipe as
measured by the Rosemount 5900S Radar Level Gauge. Adjust the Calibration
Distance in case the measured distance is not equal to the actual distance between
the Tank Reference Point and the calibration ring. See
information on tank geometry settings.
Reference Manual
Configuration
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
177
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...