4.15.3
Volume configuration
To open the Volume configuration option:
Procedure
1. Open the AMS Device Manager application.
2. Open
Configure
→
Manual Setup
→
Volume
.
The Volume tab lets you configure the Rosemount 5900S for volume
measurements. You can choose a calculation method based on one of the pre-
defined standard tank types or the Strapping Table option. The Strapping Table can
be used in case a standard tank type does not provide sufficient accuracy.
Depending on the chosen Volume Calculation Method, i.e. Ideal Sphere, Vertical or
Horizontal Cylinder, you will need to specify one or both of the two parameters
Tank Diameter (L1) and Tank Length (L2).
A Volume Offset parameter can be specified if you like to use a non-zero volume for
the zero level. This may be useful if you would like to include the product volume
below the zero level in the total volume.
Figure 4-20: Volume Configuration
Reference Manual
Configuration
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
163
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...