Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Humidity threshold 2 - Switch
Relative humidity sensor =
enabled,
Threshold 2 = below or above
1 bit
CR-T-
[1.001] switch
16
Humidity threshold 2 - Lock
Relative humidity sensor =
enabled,
Threshold 2 = below or above
Threshold lock enable = yes
1 bit
C-W--
[1.001] switch
17
Humidity threshold 2 – Value (2
bytes, from bus)
Relative humidity sensor =
enabled,
Threshold 2 = below or above
Threshold value update from bus =
yes
2 bytes
C-W--
[9.001]
temperature (°C)
18
Humidity threshold 2 – Value (1
byte, from bus)
Relative humidity sensor =
enabled,
Threshold 2 = below or above
Threshold value update from bus =
yes
1 byte
C-W--
[5.001] percentage
(0…100%)
19
Acquisition filter
The acquisition filter computes an average with a series of measured values before sending on the bus. The
parameter can have the following values:
low = average value every 4 measurements;
medium = average value every 16 measurements;
high = average value every 64 measurements.
Correction of the measured relative humidity
The sampling of the relative humidity value occurs every 10 seconds, while the display is updated every minute.
During the configuration with ETS the opportunity is given to correct the measured relative humidity value
within the offset range of – 10 % ... + 10 % (step: 1.0 %).
7.3.3
CO
2
sensor
The
CO
2
sensor
folder includes the following parameters:
Filter type for the internata data computing
CO
2
offset, applied to the measured value
Minimum change of value to send [%]
Cyclic sending interval
CO
2
control