Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 64
Parameter name
Conditions
Values
CO
2
alarm function
Threshold value
CO
2
alarm function = enabled
1000
[range 0 … 10000 ppm]
Max threshold
CO
2
alarm function = enabled
10
[range 0…100%]
Cyclic sending interval
CO
2
alarm function = enabled
no sending
[other values in the range 30 s … 120
min]
Ventilation
enabled /
disabled
CO
2
Threshold x - Type
not active
/
below only /
above only /
below and above
x = 1, 2, 3
CO
2
Threshold x
– Communication object
dimension
Type
≠ not active
1 bit value
/
1 byte unsigned value /
1 byte percentage
x = 1, 2, 3
CO
2
Threshold x
– value (below)
Type = below only, below and
above
Communication object dimension =
1 bit value
Off
/ on
x = 1, 2, 3
CO
2
Threshold x
– value (above)
Type = above only, below and
above
Communication object dimension =
1 bit value
Off
/ on
x = 1, 2, 3
CO
2
Threshold x
– value (below)
Type = below only, below and
above
Communication object dimension =
1 byte unsigned value
0
[range
0… 255]
CO
2
Threshold x
– value (above)
Type = above only, below and
above
Communication object dimension =
1 byte unsigned value
0
[range
0… 255]
CO
2
Threshold x
– percentage (below)
Type = below only, below and
above
Communication object dimension =
1 byte percentage
0
[range
0… 100 %]
CO
2
Threshold x
– percentage (above)
Type = above only, below and
above
Communication object dimension =
1 byte percentage
0
[range
0… 100 %]