Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 37
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Manual setpoint
Setpoint type =
absolute or relative
2 bytes
C-W--
[9.001] temperature (°C)
44
Heating/cooling status out
Always visible
1 bit
CR-T-
[1.100] heating/cooling
35
The communication object is updated on the bus on event of change internally elaborated by the
controller. The object is always available and contains the information about the current conduction
mode of the internal temperature controller.
Heating/cooling status in
Thermostat
function = both
heating and
cooling;
Heating
– cooling
switchover = from
bus
1 bit
C-W--
[1.100] heating/cooling
36
The communication object is received by the bus. On switching event, internal controllers of
primary and auxiliary stage (if enabled) switch their operating mode.
HVAC mode in
1 byte
C-W--
[20.102] HVAC mode
37
The device receives the operating mode (HVAC mode) from a bus device with function of
supervisor. The operating mode received through this communication object can be later
modified by the user (in this case the room thermostat switches to manual mode).
HVAC forced mode in
1 byte
C-W--
[20.102] HVAC mode
38
The communication object
allows to receive the operating mode same way as “HVAC mode in”
communication object, except the operating mode received through this objct (apart from AUTO
command) can no longer be modified by user. The user can modify the operating mode only
after “HVAC forced mode in” has sent AUTO command.
HVAC mode out
1 byte
CR-T-
[20.102] HVAC mode
39
HVAC manual mode
1 byte
CRWTU
[20.102] HVAC mode
40
Chrono active status
1 bit
CR-T-
[1.011] state
42
Manual setpoint status
Setpoint type =
absolute or relative
1 bit
CRWTU
[1.011] state
45
Setpoint in
Setpoint type =
single
s
CRWTU
[9.001] temperature (°C)
46
Building protection HVAC mode
active
1 bit
CR-T-
[1.011] state
41
About heating/cooling terminals
The application functions of the room temperature controller configurable with ETS are particularly suitable for
the control through general-purpose or dedicated KNX actuators of the following heating/cooling terminals:
0 = Cool
[1.100] DPT Heat/Cool 1 bit
1 = Heating