Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 29
Indoor CO
2
Internal sensors
CO
2
sensor =
disabled
disabled /
enabled
I
t
enables a CO
2
equivalent bus sensor.
Cyclic reading interval
Indoor CO
2
= enabled
no reading
[other values in the range 30 s … 120
min]
Antistratification temperature
disabled
/ enabled
I
t
enables a temperature bus sensor to carry out the antistratification function.
Cyclic reading interval
Antistratification temperature =
enabled
no reading
[other values in the range
30 s … 120
min]
Outdoor temperature
disabled
/ enabled
I
t
enables an outdoor temperature bus sensor.
Cyclic reading interval
Light sensor = enabled
no reading
[other values in the range
30 s … 120
min]
Coil temperature
disabled
/ enabled
I
t
enables a bus sensor for measuring the coil temperature of the conveying
fluid for heat exchange. The acquisition of the value allows realizing the hot-
start function of a fan.
Cyclic reading interval
Coil temperature = enabled
no reading
[other values in the range
30 s … 120
min]
Floor surface temperature
disabled
/ enabled
I
t
enables a bus sensor for measuring the surface temperature of a floor
heating system. The acquisition of the value allows to realize the function of
surface temperature limitation.
Cyclic reading interval
Floor surface temperature = enabled
no reading
[other values in the range
30 s … 120
min]
Flow temperature
disabled
/ enabled
I
t
enables a bus sensor for measuring the flow temperature of the conveying
fluid. The acquisition of the value allows calculating the dew-point temperature
to realize the active anticondensation protection function in surface cooling
plants (floor or ceiling).
Cyclic reading interval
Flow temperature = enabled
no reading
[other values in the range
30 s … 120
min]
Analog sensors timeout
00:05:00hh:mm:ss
[range 00:00
:00 … 18:12:15]
The field has format hh:mm:ss (hours : minutes : seconds): the default value
00:05:00 corresponds to a timeout of 5 minutes. The value 00:00:00 means
that the timeout of the analogic sensors is disabled.
Anticondensation
disabled
/ enabled
I
t
enables a bus sensor for detecting the condensation.
Signal
Anticondensation = enabled
not inverted
/ inverted