7.4
External sensors (from bus)
As “external sensors” are intended KNX-devices (or conventional sensors interfaced to the bus through KNX
devices) which send states or values to the Multisensor controller via the bus. Enabling an external sensor,
without connecting the corresponding communication object, generates a permanent alarm on the display and
suspends the thermoregulation function.
The folder
External sensors (from bus)
includes the following parameters:
Room temperature
Relative humidity
Indoor CO
2
Antistratification temperature
Outdoor temperature
Coil temperature
Floor surface temperature
Flow temperature
Analog sensors timeout
Anticondensation
Window contact X (X = 1, 2)
Presence sensor X (X = 1, 2)
Card holder contact
Digital sensors timeout
7.4.1
Parameter and communication object tables
Parameter name
Conditions
Values
Room temperature
disabled
/ enabled
It enables a bus temperature sensor. The measured value can be used to
calculate a weighted average value in combination with the temperature
sensor integrated into the device or a temperature sensor connected to a
device input.
Cyclic reading interval
Room temperature = enabled
no reading
[other values in the range
30 s … 120
min]
If the parameter is set to “no reading”, the corresponding communication object
must be updated by the remote device sending data. With any different value,
data are updated with a reading request by the room thermostat.
Relative humidity
Internal sensors
Relative humidity
sensor = disabled
disabled
/ enabled
Humidity CO dimension
Relative humidity = enabled
1 byte (DPT 5.001)
2 bytes (DPT 9.007)
Cyclic reading interval
Relative humidity = enabled
no reading
[other values in the range
30 s … 120
min]