7.3.4.1
Parameter and communication objects tables
Parameter name
Conditions
Values
TVOC sensor
enabled
disabled
The TVOC sensor is enabled as default.
Filter type
TVOC sensor = enabled
low
medium
high
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Minimum change of value to send [ppm]
TVOC sensor = enabled
0 ppm
[range -400 ppm … +400 ppm]
If the parameter is set to 0 (zero), no value is sent after a change.
Cyclic sending interval
TVOC sensor = enabled
no sending
[other values in the range 30 s … 120 min]
TVOC control
TVOC sensor = enabled
disabled
enabled
It enables the ”CO
2
control” folder.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
TVOC value
TVOC sensor = enabled
2 bytes
CR-T-
[9.008]
parts/million (ppm)
138
Note: DPT is
[9.008] parts/million (ppm), because KNX specifications do not state a corresponding
CO in [ppb] unit. Therefore, the value is scaled to the right unit internally.
Acquisition filter
The acquisition filter computes an average with a series of measured values before sending on the bus. The
parameter can have the following values:
low = average value every 4 measurements;
medium = average value every 16 measurements;
high = average value every 64 measurements.