Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 59
Parameter name
Conditions
Values
Humidity hysteresis
Dehumidification function
≠ disabled
0,8 %
[other values in the range 0,5 … 4%]
Cyclic sending interval
Dehumidification function
≠ disabled
no sending
[other values in the range 30 s … 120
min]
Disable dehumidification control from bus
Dehumidification function
≠ disabled
no
/ yes
Signal from bus
Disable dehumidification control from
bus = yes
not inverted
/ inverted
Subordinated to temperature control
Temperature control
Settings
Thermostat function = cooling or both
heating and cooling,
Temperature control
cooling
cooling type = floor radiant panels or
ceiling radiant panels,
Relative humidity
dehumidification
dehumidification function = cooling
only
no /
yes
Dehumidification start delay
Subordinated to temperature control =
no
00:05:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Value 00:00:00 means that the start delay is disabled.
Integration
no
/ yes
Temperature difference for integration
Integration = yes
1,5°C
[other values in the range 0,5 °C
… 3
°C]
Hysteresis for integration
Integration = yes
0,5 K
[other values in the range 0,2 K … 3 K]
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj.
No.
Relative humidity setpoint for
dehumidification
2 bytes
CRWTU
[9.007] humidity (%)
74
Dehumidification command
1 bit
CR-T-
[1.001] switch
76
Dehumidification water battery
command
Temperature
control
Settings
Thermostat
function = both
heating and
cooling,
Temperature
control
cooling
cooling type =
floor radiant panels
or ceiling radiant
panels,
1 bit
CR-T-
[1.001] switch
77