Installation
The device has degree of protection IP20, and is therefore suitable for use in dry interior rooms. The installation
of the device requires the following steps:
a)
fix the metallic support with the screws supplied on a wall box with suitable fixing holes. It is
recommended to install the device at a height of 150 cm;
b)
snap a square frame of the form or flank series, inserting it from the rear of the device;
c)
insert the terminal for the bus, previously connected to the bus cable, in its slot on the rear side.
Connect the sensors (if foreseen) to the device inputs. At this point it is recommended to carry out the
commissioning of the device or at least the download of the physical address;
d)
install the device on the metallic support through the spring system, tightening then the two screws
requires also to tighten the screws included in the delivery. For mounting the device follow also the
indication TOP (arrow tip pointing up) on the rear side of the device.
2.1
Connection
For the operation the device has to be connected to the bus line and addressed, configured and commissioned
with ETS (Engineering Tool Software). The connection of the KNX bus line is made with the terminal block
(red/black) included in delivery and inserted into the slot of the housing.
Characteristics of the KNX terminal block
•
spring clamping of conductors
•
4 seats for conductors for each polarity
•
terminal suitable for KNX bus cable with single-wire conductors and diameter between 0.6 and 0.8
mm
•
recommended wire stripping approx. 5 mm
•
color codification: red = + (positive) bus conductor, black = - (negative) bus conductor
Picture 2 - Connection of the device of the bus line