Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 49
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Comfort setpoint (cooling)
Setpoint type =
absolute or relative
2 bytes
CRWTU
[9.001] temperature (°C)
47
Standby setpoint (cooling)
Setpoint type =
absolute
2 bytes
CRWTU
[9.001] temperature (°C)
49
Offset standby (cooling)
Setpoint type =
relative
2 bytes
CRWTU
[9.002] temperature difference (K)
49
Economy setpoint (cooling)
Setpoint type =
absolute
2 bytes
CRWTU
[9.001] temperature (°C)
51
Offset economy (cooling)
Setpoint type =
relative
2 bytes
CRWTU
[9.002] temperature difference (K)
51
Building protection setpoint
(cooling)
2 bytes
CRWTU
[9.001] temperature (°C)
53
Cooling out command
Command
Communication
Object = separated
Control type = 2
point hysteresis or
PWM
1 bit
CR-T-
[1.001] switch
57
Cooling out command
Command
Communication
Object = separated
Control type =
continuous
1 byte
CR-T-
[5.001] percentage (0..100%)
57
Auxiliary cooling output
command
Auxiliary cooling =
enabled
1 bit
CR-T-
[1.001] switch
59
Auxiliary cooling disable
Auxiliary cooling =
enabled,
Disabled from bus =
yes
1 bit
C-W--
[1.003] enable
61
Anticondensation alarm
Active
anticondensation =
enabled
1 bit
CR-T-
[1.005] alarm
82
About anticondensation protection function
The purpose of this function is to prevent the condensation on the thermal exchange surfaces of the installation
or building when cooling is working. This function is mainly used in systems with thermal exchange consisting
in surface terminals such as for the floor and ceiling cooling radiant systems. In this case the hydraulic circuits
contain refrigerated water; usually the latent loads (due to the increase of air humidity in the room) are handled
by air-conditioning units and the temperature and humidity conditions are far from those that could cause
condensation. If this is not done in a satisfactory manner, or in case of stop of the air-conditioning units, it is