Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 75
7.12
Energy saving
In order to realize energy-saving functions, window contacts (to detect the opening of windows or doors),
presence and movement sensors and card holders can be used.
The
Energy saving
folder includes the following secondary folders:
Window contacts
Presence sensors
Card holder
The folder is available if the following conditions are satisfied:
o
Internal sensors
Temperature sensor = enabled, or
o
External sensors (from bus)
Room Temperature sensor = enabled.
7.12.1
Window contacts
The
Window contacts
secondary folder appears if at least one sensor dedicated to this function is enabled
i.e. if the following condition is verified:
o
External sensors (from bus)
Windows contact sensor 1 and/or 2 = enabled.
The
Window contacts
folder includes the following parameters:
Window contacts function
Wait time to building protection mode
7.12.1.1
Parameter and communication object tables
Parameter name
Conditions
Values
Window contacts function
disabled
/ enabled
This parameter enables the window contact function.
Wait time to building protection mode
Window contacts function = enabled
00:01:00 hh:mm:ss
[range 00:00:00 … 18:12:15]
Time interval before the automatic switching of the device to the Building protection
operating mode
Nome oggetto
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Windows contact sensor 1
(from bus)
Window contacts function =
enabled
1 bit
C-WTU
[1.019]
window/door
28
Windows contact sensor 2
(from bus)
Window contacts function =
enabled
1 bit
C-WTU
[1.019]
window/door
29