Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 22
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Temperature threshold 1 – Value
(from bus)
Temperature sensor = enabled,
Threshold 1 = below or above
Threshold value update from bus =
yes
2 bytes
C-W--
[9.001]
temperature (°C)
5
Temperature threshold 2 -
Switch
Temperature sensor = enabled,
Threshold 2 = below or above
1 bit
CR-T-
[1.001] switch
6
Temperature threshold 2 - Lock
Temperature sensor = enabled,
Threshold 2 = below or above
Threshold lock enable = yes
1 bit
C-W--
[1.001] switch
7
Temperature threshold 2 – Value
(from bus)
Temperature sensor = enabled,
Threshold 2 = below or above
Threshold value update from bus =
yes
2 bytes
C-W--
[9.001]
temperature (°C)
8
Acquisition filter
The acquisition filter calculates an average with a series of measured values before sending on the bus. The
parameter can have the following values:
low = average value every 4 measurements;
medium = average value every 16 measurements;
high = average value every 64 measurements.
Correction of the measured temperature
The sampling of the temperature value occurs every 10 seconds, while the display is updated every minute.
During the configuration with ETS the opportunity is given to correct the measured temperature value within
the offset range of - 5 °C ... + 5 °C (step: 0.1 K).
7.3.2
Relative Humidity sensor
The
Relative humidity sensor
folder includes the following parameters:
Filter type for the internata data computing
Humidity offset, applied to the measured value
Minimum change of value to send [%]
Cyclic sending interval
Threshold 1
Threshold 2
7.3.2.1
Parameter and communication objects tables
Parameter name
Conditions
Values
Relative humidity sensor
enabled
disabled
The relative humidity sensor is disabled as default.