Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 48
Parameter name
Conditions
Values
Anticondensation with probe
Cooling type = floor radiant panels or
ceiling radiant panels,
External sensors (from bus)
Anticondensation = enabled
disabled
/ enabled
Active anticondensation
Cooling type = floor radiant panels or
ceiling radiant panels,
Internal sensors
Relative humidity
sensor = enabled, or
External sensors (from bus)
Relative
humidity = enabled
disabled
enabled (project temperature)
Cooling type = floor radiant panels or
ceiling radiant panels,
Internal sensors
Relative humidity
sensor = enabled, or
External sensors (from bus)
Relative
humidity = enabled
External sensors (from bus)
Flow
temperature = enabled
disabled
enabled (comparison between flow
temperature and dew-point)
If flow temperature is lower than calculated dew point, the operating mode is cooling
and the room thermostat is in flow request, then the thermostat will close the valve and
send an alarm message over the bus.
Flow temperature (project)
Anticondensation active = enabled
19,5 °C
[other values in the range 14 °
C … 20
°C]
Only displayed if the flow temperature from external sensor (from bus) is not enabled.
Anticondensation hysteresis range
Active anticondensation = enabled (project
temperature)
0,2 K / 0,3 K / 0,4 K /
0,5
/ 0,6 K
0,8 K / 1 K / 1,5 K / 2 K / 2,5 K / 3 K
Before exiting the alarm condition, it is expected that the calculated dew-point
temperature will drop below the delivery temperature by an offset equal to the
hysteresis value.
Delay for alarm signal
Active anticondensation = enabled (project
temperature)
30 s
[other values in the range
30 s … 120
min]
Auxiliary cooling
disabled
/ enabled
Disabled from bus
Auxiliary cooling = enabled
no
/ yes
This parameter enables the activation and deactivation of the function through a
telegram from a bus device with supervising function.
Offset from setpoint
Auxiliary cooling = enabled
0,2 K /
0,3 K
/ 0,4 K / 0,5 / 0,6 K
0,8 K / 1 K / 1,5 K / 2 K / 2,5 K / 3 K
Hysteresis
Auxiliary cooling = enabled
0,2 K / 0,3 K / 0,4 K / 0,5 / 0,6 K
0,8 K /
1 K
/ 1,5 K / 2 K / 2,5 K / 3 K
Cyclic sending interval
Auxiliary cooling = enabled
hh:mm:ss (
00:00:00
)
00:00:00 means that the cyclic sending is not enabled.
Ventilation for auxiliary cooling
Cooling type = floor radiant panels or
ceiling radiant panels
disabled
/ enabled
This option allows to combine a high-inertial system as the floor radiant panels to a
low-inertial one as the fan-coils.