Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 62
7.8.3
Calculated psychrometric values
The secondary folder
Calculated psychrometric values
includes the following parameters:
Dew-point temperature
Cyclic sending interval
Min. change of value to send [K]
Disable from bus
7.8.3.1
Parameter and communication object tables
Parameter name
Conditions
Values
Dew-point temperature
disabled
/ enabled
The dew-point temperature, if sent on the bus, allows to implement an active
anticondensation protection with recalibration of the flow conditions of the
conveying fluid if each mixing group has its own control device. If the
thermostat is installed in an environment where no air conditioning is foreseen
(e.g. toilets), it is better to exclude that environment from the control by
disabling the dew-point temperature parameter.
Cyclic sending interval
Dew-point temperature = enabled
no sending
[other values in the range 30 s … 120
min]
Min. change of value to send [K]
Dew-point temperature = enabled
0,2 K
/ no sending
[other values in the range 0,2 … 3 K]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Dew-point temperature
Dew-point temperature =
enabled
2 bytes
CR-T-
[9.001]
temperature °C
73