Parameter name
Conditions
Values
TVOC Threshold x
– Communication object
dimension
Type ≠ not active
1 bit value
/
1 byte unsigned value /
1 byte percentage
x = 1, 2, 3
TVOC Threshold x
– value (below)
Type = below only, below and
above
Communication object dimension
= 1 bit value
Off
/ on
x = 1, 2, 3
TVOC Threshold x
– value (above)
Type = above only, below and
above
Communication object dimension
= 1 bit value
Off
/ on
x = 1, 2, 3
TVOC Threshold x
– value (below)
Type = below only, below and
above
Communication object dimension
= 1 byte unsigned value
0
[range 0… 255]
TVOC Threshold x
– value (above)
Type = above only, below and
above
Communication object dimension
= 1 byte unsigned value
0
[range 0… 255]
TVOC Threshold x
– percentage (below)
Type = below only, below and
above
Communication object dimension
= 1 byte percentage
0
[range 0… 100 %]
TVOC Threshold x
– percentage (above)
Type = above only, below and
above
Communication object dimension
= 1 byte percentage
0
[range 0… 100 %]
TVOC Threshold x
– cyclic sending interval
Type ≠ not active
no sending
[other values in the 30 s … 120 min
range]
x = 1, 2, 3
TVOC Threshold x
– Lock enable
Type ≠ not active
no
/ yes
x = 1, 2, 3
TVOC Threshold x
– Behaviour at lock
Lock enable = yes
none
/ send value
x = 1, 2, 3
TVOC Threshold x
– Value
Communication object dimension
= 1 bit value
Lock enable = yes
Behaviour at lock = send value
off
/ on
x = 1, 2, 3
TVOC Threshold x
– Value
Communication object dimension
= 1 byte unsigned value
Lock enable = yes
Behaviour at lock = send value
0
[range 0… 255]
x = 1, 2, 3