9.7
Auxiliary stage with fan coil
In some heating / cooling system, an auxiliary fan coil system which operates on air volumes is paired with an
high inertial system (such as floor radiant panels): EK-ET2-TP Multisensor controller can be easily configured
for this kind of application.
Picture 21
Picture 22
As for the configuration of the auxiliary stage, you can apply the same rules already expressed in the ON/OFF
and continuous fan coil control paragraph. Particularly relevant here is the auxiliary stage intervention offset,
ΔT
Offset
, which matches the parameter
Setpoint difference
in
Heating and/or cooling
folder. By configuring this
parameter (which can be different between heating and cooling if command communication objects are
separated) to 0 K, the radiant panel and the fan coil work as two heating and/or cooling devices in parallel.
Otherwise, if
Setpoint difference
> 0 K
,
the fan coil intervenes very quickly in the first tuning stages and leaves
to the radiant panel the job of reaching the desired temperature.
SP1
Tset
SP2
SP3
Hysteresis
T Ambient
Tset
T Ambient
Hysteresis
OFF
SP1
SP2
SP3
OFF
Threshold TS1
Threshold TS2
Threshold TS3
(T Setpoint
– T Ambient)
Threshold
TS1
Threshold
TS2
Threshold TS3
(T Ambient
– T Setpoint)
TOffset
TOffset
T ambient
OFF
ON
Tset
Thysteresis
T ambient
OFF
ON
Tset
Thysteresis
TOffset
TOffset