Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 80
Parameter name
Conditions
Values
x = 1, 2, 3, 4
By denying the logical state of the corresponding input, it is possible to implement
complex combinatorial logics. Example: Output=(NOT(Logic object 1) OR Logic
object 2)).
Logic object x read at startup
Logic function = enabled
Logic object x = enabled
no
/ yes
x = 1, 2, 3, 4
Logic object x default value
Logic function = enabled
Logic object x = enabled
none
/ off / on
x = 1, 2, 3, 4
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj. No.
Logic function X – Input 1
Logic function X = enabled
Logic object 1 = enabled
1 bit
C-WTU
[1.001] switch
98, 103, 108, 113,
118, 123, 128, 133
X = 1, …, 8
Logic function X
– Input 2
Logic function X = enabled
Logic object 2 = enabled
1 bit
C-WTU
[1.001] switch
99, 104, 109, 114,
119, 124, 129, 134
X = 1, …, 8
Logic function X – Input 3
Logic function X = enabled
Logic object 3 = enabled
1 bit
C-WTU
[1.001] switch
100, 105, 110, 115,
120, 125, 130, 135
X = 1, …, 8
Logic function X
– Input 4
Logic function X = enabled
Logic object 4 = enabled
1 bit
C-WTU
[1.001] switch
101, 106, 111, 116,
121, 126, 131, 136
X = 1, …, 8
Logic function X
– Output
Logic function X = enabled
At least one logic object
enabled
1 bit
CR-T-
[1.001] switch
102, 107, 112, 117,
122, 127, 132, 137
X = 1, …, 8