Parameter name
Conditions
Values
Threshold 2 < Value < threshold 3
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte percentage
0 %
[range 0… 100 %]
Value > threshold 3
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte percentage
0 %
[range 0… 100 %]
Min. change of value to send [%]
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte percentage (continuous
speed)
10 %
[range 2… 40 %]
CO
2
- hysteresis
CO
2
ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
150 ppm
(other values in the 50 … 500 ppm range)
Min. CO
2
[ppm]
CO
2
ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
400 ppm
(other values in the 0 … 10000 ppm
range)
Max. CO
2
[ppm]
CO
2
ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
5000 ppm
(other values in the 0 … 10000 ppm
range)
CO
2
- Min. output [%]
CO
2
ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
0 %
[range 0… 100 %]
CO
2
- Max. output [%]
CO
2
ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
100 %
[range 0… 100 %]
TVOC - hysteresis
TVOC ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
60 ppb
(other values in the 20 … 200 ppb range)
Min. TVOC [ppb]
TVOC ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
250 ppb
(other values in the 0 … 10000 ppb
range)
Max. TVOC [ppb]
TVOC ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
400 ppb
(o
ther values in the 0 … 10000 ppb
range)