Parameter name
Conditions
Values
Economy temp. setpoint [°C]
Setpoint type = absolute or relative
16
[range
10 … 50]
For a correct operation of the device the economy temperature setpoint has to be <
standby temperature setpoint.
Building protection temp. setpoint [°C]
7
[range
2 … 10]
Heating type
radiators
electric
fan-coils
floor radiant panels
ceiling radiant panels
It defines the terminal used for the thermal exchange in the room. The choice affects
the parameters of the PWM control algorithm (Proportional band and Integral time) and
the control options.
Control type
2 point hysteresis
PWM (pulse width modulation)
Continuous
6-way valve
Hysteresis [K]
Control type = 2 point hysteresis
0,3 K
[other values in the range
0,2 K … 3 K]
Hysteresis position
Heating type = floor radiant panels,
ceiling radiant panels,
Control type = 2 point hysteresis
below
/ above
The above hysteresis is suitable in case of special applications requiring mixing group
control.
Cyclic sending interval
Control type = 2 point hysteresis,
continuous or 6-way valve
no sending
[other values in the range 30 s … 120
min]
Proportional band [0,1 K]
Control type = continuous, PWM or 6-way
valve
40
[range
5 … 100]
The value is in tenths of Kelvin (K) degree.
*) The field contains a preset value that depend on the selected heating type (the value
can be modified):
radiators: 50 ( 5 K)
electric: 40 (4 K)
fan-coils: 40 (4 K)
floor radiant panels: 50 (5 K)
ceiling radiant panels: 50 (5 K)
The value of the parameter Proportional band represents the max difference between
the setpoint temperature and the measured temperature that causes the max control
output.
Integral time [min]
Control type = continuous, PWM or 6-way
valve
90
[other values in the range
0 … 255 min]
*) The field contains a preset value that depend on the selected heating type (the value
can be modified):
radiators: 150 min
electric: 100 min
fan-coils: 90 min
floor radiant panels: 240 min
ceiling radiant panels: 180 min