Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 44
Parameter name
Conditions
Values
Ventilation for auxiliary heating
Command Communication
Object = unique
Heating type = floor radiant
panels or ceiling radiant panels
OR
Command Communication
Object = separated
Heating type = radiators,
electric, floor radiant panels or
ceiling radiant panels
disabled
/ enabled
This option allows to match a system with high inertia as the floor radiant panels
(hydronic version) with a system with low inertia as the fan-coils.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Setpoint in
Setpoint type = single
2 bytes
CRWTU
[9.001] temperature (°C)
46
Comfort setpoint (heating)
Setpoint type = absolute
or relative
2 bytes
CRWTU
[9.001] temperature (°C)
46
Standby setpoint (heating)
Setpoint type = absolute
2 bytes
CRWTU
[9.001] temperature (°C)
48
Offset standby (heating)
Setpoint type = relative
2 bytes
CRWTU
[9.002] temperature difference
(K)
48
Economy setpoint (heating)
Setpoint type = absolute
2 bytes
CRWTU
[9.001] temperature (°C)
50
Offset economy (heating)
Setpoint type = relative
2 bytes
CRWTU
[9.002] temperature difference
(K)
50
Building protection setpoint
(heating)
2 bytes
CRWTU
[9.001] temperature (°C)
52
Heating out command
Command
communication object =
separated,
Control type = 2 points
hysteresis or PWM
1 bit
CR-T-
[1.001] switch
56
Heating out command
Command
communication object =
separated,
Control type = continuous
1 byte
CR-T-
[5.001] percentage (0..100%)
56
Heating and cooling out
command
Command
communication object =
unique,
Tipo Control type = 2
points hysteresis or PWM
1 bit
CR-T-
[1.001] switch
56