Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 46
7.7.3
Cooling
The
Cooling
folder includes the following parameters:
Comfort temp. setpoint [°C]
Standby temperature setpoint [°C]
Economy temp. setpoint [°C]
Building protection temp. setpoint [°C]
Cooling type
Control type
Hysteresis [K]
Hysteresis position
Cyclic sending interval
Proportional band [0,1 K]
Integral time [min]
PWM cycle time
Min. change of value to send [%]
Min. control value [%]
Max. control value [%]
Anticondensation with probe
Active anticondensation
Flow temperature (project)
Anticondensation hysteresis range
Delay for alarm signal
Auxiliary cooling
Disabled from bus
Offset from setpoint
Hysteresis [K]
Cyclic sending interval
Ventilation for auxiliary cooling
7.7.3.1
Parameter and communication object tables
Conditions:
General
Thermostat function = cooling or both heating and cooling.
Parameter name
Conditions
Values
Comfort temp. setpoint [°C]
23
[range
10 … 50]
Building protection temp. setpoint [°C]
36
[range
30 … 50]
Standby temp. setpoint [°C]
Setpoint type = absolute or relative
26
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be >
comfort temperature setpoint.
Economy temp. setpoint [°C]
Setpoint type = absolute or relative
28
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be >
economy temperature setpoint.