Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 70
Parameter name
Conditions
Values
Value < threshold 1
– bit x
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
4 single bit values
off
/ on
x = 1, 2, 3, 4
Threshold 1 < Value < threshold 2
– bit x
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
4 single bit values
off
/ on
x = 1, 2, 3, 4
Threshold 2 < Value < threshold 3
– bit x
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
4 single bit values
off
/ on
x = 1, 2, 3, 4
Threshold 3 < Value
– bit x
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
4 single bit values
off
/ on
x = 1, 2, 3, 4
Value < threshold 1
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte unsigned value
0
[range 0… 255]
Threshold 1 < Value < threshold 2
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte unsigned value
0
[range 0… 255]
Threshold 2 < Value < threshold 3
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte unsigned value
0
[range 0… 255]
Value > threshold 3
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte unsigned value
0
[range 0… 255]
Value < threshold 1
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte percentage
0 %
[range 0… 100 %]
Threshold 1 < Value < threshold 2
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte percentage
0 %
[range 0… 100 %]