Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 72
Parameter name
Conditions
Values
TVOC - Min. output [%]
TVOC ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
0 %
[range 0… 100 %]
TVOC - Max. output [%]
TVOC ventilation = enabled
Communication object dimension =
1 byte percentage (continuous
speed)
100 %
[range 0… 100 %]
Ventilation lock
CO
2
and/or TVOC ventilation =
enabled
disabled
/ enabled
Behaviour at lock
CO
2
and/or TVOC ventilation =
enabled
Ventilation lock = enabled
none
/ send value
Behaviour after bus on
CO
2
and/or TVOC ventilation =
enabled
Ventilation lock = enabled
previous state
/
lock /
unlock
Lock value
– bit x
CO
2
ventilation = enabled
Communication object dimension =
4 single bit values
CO
2
ventilation lock = enabled
Behaviour at lock = send value
off
/ on
x = 1, 2, 3, 4
Lock value
CO
2
ventilation = enabled
Communication object dimension =
1 byte unsigned value
CO
2
ventilation lock = enabled
Behaviour at lock = send value
0
[range 0… 255]
Lock value
CO
2
and/or TVOC ventilation =
enabled
Communication object dimension =
1 byte percentage or 1 byte
percentage (continuous speed)
CO
2
ventilation lock = enabled
Behaviour at lock = send value
0 %
[range 0… 100 %]
Disable ventilation from bus
CO
2
and/or TVOC ventilation =
enabled
no
/ yes
Signal from bus
CO
2
and/or TVOC ventilation =
enabled
Disable ventilation from bus = yes
not inverted
/ inverted
Time scheduled ventilation
Time scheduled ventilation =
enabled
disabled
/ enabled
Please see Note 1.
Frequency
Time scheduled ventilation =
enabled
30
(other
values in the 5 … 60 min range)