The definiton of hyteresis levels must be directly performed on the fan coil actuator. The application program
offers the parameter
Proportional band
, which has the the same value for both heating and cooling: this
parameter determines the fan intervention gradient. The parameter
Min. change of value to send [%]
is defined
in order to limit the frame exchange on the bus.
The 1-byte communication object
Fan continuous speed
(62) changes continuously according to the
curve shown in Picture 18. Please refer to the previous paragraph to evaluate differences with the
1-2-3-speed control, where the same communication object has discrete values.