Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 54
Parameter name
Conditions
Values
Signal from bus
Disable ventilation from bus =
yes
not inverted
inverted
Fan start delay
0 s
[other values in the range 10 s …
12 min]
This parameter is also available if the hot-start function is active
(through measuring of the conveying fluid temperature at the battery
for the thermal exchange). The function is active in both seasonal
modes (heating and cooling).
Fan stop delay
0 s
[other values in the range 10 s …
12 min]
The function allows prolonging the operation of the ventilator,
dissipating in the room the residual heat or cool present in battery for
the thermal exchange. The function is active in both seasonal modes
(heating and cooling).
Cyclic sending interval
no sending
[other values in the range 30 s …
120 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Fan continuous speed
Control type =
continuous
regulation
1 byte
CR-T-
[5.001] percentage (0..100%)
62
Fan speed 1
Control type = 1, 2
or 3 speeds
1 bit
CR-T-
[1.001] switch
63
Fan speed 2
Control type = 2 or
3 speeds
1 bit
CR-T-
[1.001] switch
64
Fan speed 3
Control type = 3
speeds
1 bit
CR-T-
[1.001] switch
65
Fan control disable
Disable ventilation
from bus = yes
1 bit
C-W--
[1.002] boolean
66
Fan manual speed
1 byte
CRW-U
[5.010] counter pulses (0…255)
68
Fan speed
1 byte
CR-T-
[5.010] counter pulses (0…255)
67
Fan manual active status
1 bit
CRWT-
[1.011] state
70
Fan manual speed percentage
1 byte
CR-T-
[5.001] percentage
69
Fan manual speed off status
1 bit
CR-T-
[1.011] state
71