Appendix C—Optional Communication Cards
288
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
Class Attributes
Sr. No.
ID
Description
Access Rule
Data Type
Remarks/Default
1
1 (0x1)
Revision
Get
UINT
1
2
2 (0x2)
Max Instance
Get
UINT
2
3
3 (0x3)
Number of Instances
Get
UINT
2
4
6 (0x6)
Maximum ID Class Attribute
Get
UINT
9
5
7 (0x7)
Maximum ID Instance Attribute
Get
UINT
7
6
8 (0x8)
Entry Port
Get
UINT
2
7
9 (0x9)
Port Instance Info
Get
Array of Struct of
Port Type
UINT
See Instance attribute
Port Number
UINT
See Instance attribute
Instance Attributes
Number of instances: 2
Sr. No.
ID
Description
Access Rule
Data Type
Remarks/Default
1
1 (0x1)
Port Type
Get
UINT
4
2
2 (0x2)
Port Number
Get
UINT
1 or 2
3
3 (0x3)
Link Object
Get
Struct of:
Path Length
UINT
2
Link Path
Padded EPATH
20 F5 24 01
4
4 (0x4)
Port Name
Get
Short String
Ethernet/IP Port (in ASCII)
7
7 (0x7)
Port Number and Node address
Get
Padded EPATH
Active IP address (in ASCII)
Table 115. TCP/IP Object—Class 0xF5 (245)
Class Services
Service
Code
Service Name
0x0E
Get Attribute Single
0x01
Get Attributes All
Instance Services
Service
Code
Service Name
0x0E
Get Attribute Single
0x10
Set Attribute Single
0x01
Get Attributes All
Class Services
Sr. No.
ID
Description
Access Rule
Data
Remarks/Default
1
1 (0x1)
Revision
Get
UINT
4
2
2 (0x2)
Max Instance
Get
UINT
1
3
3 (0x3)
Number of instances
Get
UINT
1
4
4 (0x4)
Optional attribute list
Get
Array of UINT
04 00 08 00 09 00 0A 00 0B 00
5
6 (0x6)
Maximum ID Class Attribute
Get
UINT
6
7 (0x7)
Maximum ID Instance Attribute
Get
UINT
0B 00
Table 114. Port Object—Class 0xF4 (244), continued