Chapter 5—System Configuration and Operation
72
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
Figure 67. 120 Vac Inputs and 120/230 Vac Outputs/C445 Power
Notes:
1.
The inputs on the Base Control Module are only used by
this Operation Mode if Fieldwire is selected for one of
the control sources. If Fieldwire is not the Local or
Remote control source, all 4 inputs may be used as
general purpose inputs.
2.
Outputs 2 and 3 may be used as general purpose
outputs for this Operation Mode.
3.
If Fieldwire is the Local control source, Input 3 is the
Remote input. When power is applied to Input 3, the
C445 will be in Remote mode.
4.
If Fieldwire is the Remote control source and 2-wire
control (default) is selected, Inputs 2 and 3 are unused
by this operation mode.
5.
If 3-wire control is selected along with Fieldwire for
either control source, Input 2 is Permissive.
6.
Fusing: Although C445 product listings do not require
fusing on the high impedance line voltage measurement
inputs, it may be necessary to provide overcurrent
protection of the supply leads in accordance with
applicable final installation specific local, state and
national electrical codes.
Q11
CH1
T1
T2
V1
V2
V3
C445M...
I1
I2
C445BA-SA...
CH1
CH2
CH1
I3
I4
IC
Q1
Q1
Q2
Q2
Q3
C
Q3
C
D0
D1
CH2
PTC
MOTOR
3~
L2
L3
PE
L1
Optional Modbus
Q11
Q1
PE
N
L
IC
IC
(+) Us
(-) Us
120/240 VAC
FB1
FERRITE
RESET
REMOTE
RUN
(+) Uc
(-) Uc
120 VAC
C445U…