Appendix D—Modbus Register Map
318
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
600
Fieldbus Motor Control
BYTE RW
Bitfield
USB Lock
Fieldbus Motor Control - Run 1 Command Bit: This bit is Profile dependent.
For example, this is the Run bit for a FVNR motor application or the Run
FWD bit for a FVR applications. - Run 2 Command Bit: This bit is Profile
dependent. For example, this is not used for a FVNR motor application or
is the Run REV Run for a FVR applications. - Fault Reset: This resets an
active fault if the fault condition is no longer present. - Test Trip: This
allows the user to trip the unit for test purposes. Use Fault Reset to reset
the test trip condition.
601
Output Control
BYTE RW
Bitfield
ON / OFF Control for Available Base Control Module Field Outputs. The
Profile type dictates which of these outputs are available as general
purpose outputs. For example, Outputs 2 and 3 are available when the
Direct profile is selected, while only Output 3 is available when the
Reverser Profile is selected. The bits are assigned to specific physical
outputs in the Operation Mode category and the parameters are called
Output x Function Select.
602
Remote Feedback Signal
Parameter
BYTE RW
Bitfield
This parameter only applies if the Operation mode being used includes
digital feedback (Solenoid, MCCB Actuation and Contactor Feeder) and
the selection for the Feedback Signal Source Select parameter is
“Feedback Signals Provided by Network”. If both of these conditions are
met, then this parameter is a read only parameter that allows monitoring
the state of the inputs with this software. Inputs 2 and 3 indicate the
following based on the operation mode. Solenoid: Input 2 (bit 1) = Open,
Input 3 (bit 2) = Closed Contactor/Feeder: Input 2 (Bit 1) = AUX On MCCB
Feeder: Input 2 (Bit 1) = CB On, Input 3 (Bit 2) = CB Alarm
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Bit
Description
Coil
0
Run1 command bit
9585
1
Run2 command bit
9586
2
Switch Control To Remote
9587
3
Reset fault bit
9588
4
Reserved bit
9589
5
Test trip the device bit
9590
Bit
Description
Coil
0
Bit 0
9601
1
Bit 1
9602
2
Bit 2
9603
3
Bit 3
9604
Bit
Description
Coil
0
Network feedback input I1
9617
1
Network feedback input I2
9618
2
Network feedback input I3
9619
3
Network feedback input I4
9620
4
Network feedback input I5
9621
5
Network feedback input I6
9622
6
Network feedback input I7
9623
7
Network feedback input I8
9624