Chapter 5—System Configuration and Operation
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
95
Bit 5
0 = no inhibit present
1= C445 control inhibit present
Bit 6
0 = C445 not ready (fault and/or inhibit present)
1= C445 ready for control (No fault or inhibit present)
Bit 7
0 = valve is in not desired end position
1= valve is in desired end position
The following conditions will set the InPos bit in the status
word, signaling the valve has reached the desired end
position.
Normally closed valve
●
Energize command is active and open feedback detected
●
De-energize command is active and Closed feedback
detected
Normally open valve
●
Energize command is active and closed feedback detected
●
De-energize command is active and open feedback
detected.