Appendix D—Modbus Register Map
308
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
313
Active Warning
UINT16 RO
Enum
Current Active Warning, continued
314
Active Inhibit
UINT16 RO
Enum
Current Active Inhibit
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Value
Description
1025
Logic User Warning 26
1026
Logic User Warning 27
1027
Logic User Warning 28
1028
Logic User Warning 29
1029
Logic User Warning 30
1030
Logic User Warning 31
1031
Logic User Warning 32
1032
Logic User Warning 33
1033
Logic User Warning 34
1034
Logic User Warning 35
1035
Logic User Warning 36
1036
Logic User Warning 37
1037
Logic User Warning 38
1038
Logic User Warning 39
1039
Logic User Warning 40
1040
Logic User Warning 41
1041
Logic User Warning 42
1042
Logic User Warning 43
1043
Logic User Warning 44
1044
Logic User Warning 45
1045
Logic User Warning 46
1046
Logic User Warning 47
1047
Logic User Warning 48
1048
Logic User Warning 49
1049
Logic User Warning 50
Value
Description
0
No inhibits
1
Incorrect configuration. See configuration inhibit reason
2
A soft reset is required
3
Backspin prevention
4
Under voltage restart timer active
5
Control voltage is low
6
Under voltage condition
7
Voltage unbalance
8
Starts per hour limit has been exceeded
9
Over voltage condition
10
ELC IO hardware does not match the configuration
11
Run interlock input is open