Appendix C—Optional Communication Cards
262
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
Table 96. Discrete Input Object—Class 0x8 (8)
Class Services
Service
code
Service Name
0x0E
Get Attribute Single
Instance Services
Service
code
Service Name
0x0E
Get Attribute Single
0x10
Set Attribute Single
Class Attributes
Sr. No.
Attribute ID
Access Rule
Data Type
Name
Attribute Description
1
1 (0x1)
Get
UINT
Revision
Revision of this object
2
2 (0x2)
Get
UINT
Max. Instance
Maximum instance number of an object currently
created in this class level of the device.
3
3 (0x3)
Get
UINT
Number of Instances
Number of object instances currently created at
this class level of the device.
Instance Attributes
Sr. No.
Instance
Attribute ID
Access
Data Type
Attribute Name
Attribute Description
1
1 (0x1),
3 (0x3)
Get
BOOL
value
ON/OFF Status of BCM Digital Inputs:
0: OFF, 1: ON
Instance 1- BCM Digital i/p-1
2
2 (0x2)
3 (0x3)
Get
BOOL
value
ON/OFF Status of BCM Digital Inputs:
0: OFF, 1: ON
Instance 2-BCM Digital i/p-2
3
3 (0x3)
3 (0x3)
Get
BOOL
value
ON/OFF Status of BCM Digital Inputs:
0: OFF, 1: ON
Instance 3-Digital i/p-3
4
4 (0x4)
3 (0x3)
Get
BOOL
value
ON/OFF Status of BCM Digital Inputs:
0: OFF, 1: ON
Instance 4-BCM Digital i/p-4
9
1 (0x1)
101 (0x65)
Get/Set
UINT
Debounce
BCM Digital i/p-1 debounce time. Applies to both
raising & Falling edge. (mSec)
10
2 (0x2)
101 (0x65)
Get/Set
UINT
Debounce
BCM Digital i/p-2 debounce time. Applies to both
raising & Falling edge. (mSec)
11
3 (0x3)
101 (0x65)
Get/Set
UINT
Debounce
BCM Digital i/p-3 debounce time. Applies to both
raising & Falling edge. (mSec)
12
4 (0x4)
101 (0x65)
Get/Set
UINT
Debounce
BCM Digital i/p-4 debounce time. Applies to both
raising & Falling edge. (mSec)