Appendix C—Optional Communication Cards
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
235
Note:
To use Bit 2 in Output Instances 106, 127, 128 and 129 to switch the Active Control
source between Local (0) and Remote (1), the “Allow Remote Control Switch” must
be Enabled (True). This parameter can be found in the Operation Mode category,
under Advanced Parameters.
Output Instance 105 (0x69): Basic Output Control
Length = 2 Bytes
Byte
Offset
Size
(bytes)
Name
Description
0
2
Basic Overload
w/Relay
Basic Overload with Relays
Bit 0 = Output #1
Bit 1 = Output #2
Bit 2 = Output #3 (set)
Bit 3 = Fault Reset
Bit 4 = Output #3 (reset)
Bit 5 = Test Trip
Bit 6 to 15 = reserved
Output Instance 106 (0x6A): Extended Motor Control 2
Length = 2 Bytes
Byte
Offset
Size
(bytes)
Name
Description
0
2
Basic Control Relay
Basic Control Bits:
(Byte1: NETCTRL_CONTROL_WORD)
(Byte2: BCM_FIELD_OUTPUTS)
Bit 0: Run1
Bit 1: Run2
Bit 2: Switch Control to Remote (see note below)
Bit 3: Fault Reset
Bit 4: Control from network / Switch to remote
Bit 5: Test Trip
Bit 6: Reserved
Bit 7: Reserved
Bit 8: Output #1 (Conditional. Depends on profile selected)
Bit 9: Output #2 (Conditional. Depends on profile selected)
Bit 10: Output #3 (set) (Conditional. Depends on profile selected)
Bit 11: Output #3 (reset) (Conditional. Depends on profile selected)
Bits 12–15: Reserved
Output Instance 123 (0x7B): Basic Starter Relay with Analog and Digital Outputs
Length = 8 Bytes
Byte
Offset
Size
(bytes)
Name
Description
0
2
Basic Starter with
Analog and Digital
Outputs
Vendor specific Basic starter
Bit 0 = Run1
Bit 1 = Run2
Bit 2 = Reserved
Bit 3 = Fault Reset
Bits 4 to 15 = Reserved
2
2
Digital Outputs
Bits 0-7 = Outputs for first digital output card
Bits 8-15 = Outputs for second digital output card
4
4
Analog Outputs
2 Output words of data for 2 analog outputs