Appendix D—Modbus Register Map
306
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
312
Active Fault
UINT16 RO
Default: 0
Enum
Current Active Fault, continued
313
Active Warning
UINT16 RO
Enum
Current Active Warning
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Value
Description
1043
Logic User Fault 44
1044
Logic User Fault 45
1045
Logic User Fault 46
1046
Logic User Fault 47
1047
Logic User Fault 48
1048
Logic User Fault 49
1049
Logic User Fault 50
Value
Description
0
No Warnings
1
Under voltage
2
Over voltage
3
Reserved
4
Ground current warning
5
Current phase loss
6
Current unbalance
7
Instantaneous over current
8
Jam
9
PF Deviation
10
Voltage phase loss
11
Voltage unbalance
12
Frequency deviation fast
13
Frequency deviation slow
14
Under current
15
High power
16
Low power
17
Contactor failure
18
Starts limit exceeded
19
Overload
20
Stall
21
Phase rotation mismatch
22
PTC - See PTC State for details
23
Peak demand
24
Measurement Module warning
25
Real Time Clock requires setting (has not been set)
26
RTC Battery Low. Replacement is recommended
27
Device ambient temperature high
28
MM high ambient temperature
29
UI high ambient temperature
30
Option card high ambient temperature
31
Ground fault module high ambient temperature