Chapter 9—C445 Logic Engine and Expansion I/O
202
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
Note that even though Cyclic Module 8 contains 6 output bytes or 3 output words,
once Motor Control bits are assigned, only 2 additional words are available to assign
to other parameters. As shown below, these final 2 output words are assigned to
Remote Digital Output 0 and 1. This means there are four 8 point digital expansion
output cards connected to the C445. The Motor Control bits will be the first word
sent to the C445, followed by the other 2 assigned words for controlling expansion
output modules in this case.