Chapter 5—System Configuration and Operation
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
105
Figure 107. 120 Vac Inputs and 120/230 Vac Outputs/C445 Power
Notes:
1.
The inputs on the Base Control Module are only used by
this Operation Mode if Fieldwire is selected for one of
the control sources. If Fieldwire is not the Local or
Remote control source, all 4 inputs may be used as
general purpose inputs or can be selected as the
feedback source for the feeder’s aux_on contact.
2.
Outputs 2 and 3 may be used as general purpose
outputs for this Operation Mode.
3.
If Fieldwire is the Local control source, Input 3 is the
Remote input. When power is applied to Input 3, the
C445 will be in Remote mode.
4.
If Fieldwire is the Remote control source and 2-wire
control (default) is selected, Inputs 2 and 3 are unused
by this operation mode. Either may be used as the
feedback source for the feeder’s aux_on contact.
5.
Fusing: Although C445 product listings do not require
fusing on the high impedance line voltage measurement
inputs, it may be necessary to provide overcurrent
protection of the supply leads in accordance with
applicable final installation specific local, state and
national electrical codes.
6.
C445UC... control user interfaces offer 4 additional
24 Vdc digital inputs for general purpose use. An input
can also be used as the feedback source for the feeder’s
aux_on contact.
CLOSE
L2
L3
PE
L1
CH1
T1
T2
V1
V2
V3
C445M...
I1
I2
C445BA-SA...
CH1
CH2
I3
I4
IC
IC
IC
Q1
Q1
Q2
Q2
Q3
C
Q3
C
D0
D1
PTC
MOTOR
3~
Optional Modbus
Q11
Q1
Q11
RESET
REMOTE
CH1
C445U…
CH2
PE
N
L
FB1
FERRITE
(+) Us
(-) Us
120/240 VAC
(+) Uc
120 VAC
(-) Uc