Appendix C—Optional Communication Cards
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
267
Instance Attributes
Sr. No.
ID
Access Rule
Data Type
Description
19
108 (0x6C) Get
UINT
Active Fault
0: No Faults
1: Undervoltage
2: Overvoltage
3: Reserved
4: Ground current
5: Current phase loss
6: Current unbalance
7: Instantaneous over current
8: Jam
9: PF deviation
10: Voltage phase loss
11: Voltage unbalance
12: Freq deviation fast
13: Freq deviation slow
14: Under current
15: High power
16: Low power
17: Contactor failure
18: Exceeds starts limit
19: Overload
20: Stall
21: Phase rotation
22: PTC - See PTC State for details
23: Under voltage restart
24: Measurement Module fault
25: Communication loss on active fieldbus
26: Measurement Module not available or comm loss with
the module
27: User Interface not available or comm loss with the module
28: Test trip device fault
29: Option card not available or comm loss with the module
30: RTC Option board NV memory fail
31: Currently connected User Interface does not match with
what was connected before.
32: Currently connected Measurement Module does not match
with what was connected before.
33: Currently connected Comm Card does not match with
what was connected before
38: Ground Fault Module firmware is incompatible
39: Ground Fault Module communication loss
40: Ground Fault Module mismatch
41: Ground Fault Module CT open
42: Ground Fault Module CT shorted
43: Ground Fault Module CT no cal
44: HRGF Pulse Detect
200–232: Logic engine faults
500: Internal - Communication loss with Power Supply Board
501: Internal - Power Supply Board is not responding to SPI
502: Internal - Checksums in NV Memory (F-RAM) didn't match
during read (neither pair)
503: Internal - Checksums in NV Memory (F-RAM) didn't match
during write (neither pair)
504: Internal - Expected backup memory RTC module is missing
505: Internal - Expected backup memory RTC module is
mismatched with actual
506: Internal - Backup Memory RTC module has NV fault.
507: Internal - Serial flash memory fault in BCM
508: Internal - Mapping Error
511: Internal Ground Fault Module NV memory error
1000–1049: Logic User faults
Table 98. Control Supervisor Object—Class 0x29 (41), continued