Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
399
2559
Fault/Warning configuration
BYTE RW NV
Array size: 4
Default: 0
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
Fault/Warning configuration - When a bit is set to 0, a fault is thrown,
when set to 1, a warning is thrown.
2561
Logic error info - Program Id
UINT16 RO
Default: 0
Logic error info - Program Id
Logic error info - Program Id
2562
Logic error info - Program
Counter
UINT32 RO
Default: 0
Logic error info - Program Counter
Logic error info - Program Counter
2564
Logic error info - Error Data
UINT32 RO
Default: 0
Logic error info - Error Data
Logic error info - Error Data
2566
Logic Run Control
BYTE RW NV
Default: 0
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
Logic Run Control
2567
Logic Run Status
BYTE RO
Default: 0
Bitfield
Logic Run Status
2568
ELC IO Speciality Module
config location
UINT8 RW NV
Default: 0
Enum
Admin Lock
Backup Mem
ELC IO Speciality Module config location
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Bit
Description
Coil
0
Logic program underrun
40929
1
Logic program overrun
40930
2
Logic task watchdog
40931
3
Logic instruction invalid instance number
40932
4
Logic instruction invalid argument
40933
5
Logic math - divide by zero
40934
6
Logic math - underflow
40935
7
Logic math - overflow
40936
8
ELC IO Comm loss
40937
9
ELC IO Comm error
40938
10
Generic Modbus slave comm loss
40939
11
Generic Modbus slave comm error
40940
12
Logic Program accessing ELC IO but ELC IO not
configured
40941
Bit
Description
Coil
0
Run
41041
Bit
Description
Coil
0
Logic Running
41057
Bit
Description
Coil
0
C445
ELC10