Chapter 9—C445 Logic Engine and Expansion I/O
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
161
RS_D—Reset Dominant Bi-Stable with Data Input
The RS_D function block performs as an RS function block with SET and RESET when
LOAD is FALSE. But, when LOAD is set to TRUE, DATA is copied to the output.
SET
RESET
DATA
LOAD
OUT (Previous)
OUT
0
0
x
0
0
0
0
0
x
0
1
1
1
0
x
0
0
1
1
0
x
0
1
1
x
0
1
1
x
1
x
0
0
1
x
0
x
1
x
x
x
0
Parameter
Data type
Description
SET
BOOL
Set input
DATA
BOOL
Data input, will be copied to OUT when LOAD = TRUE
LOAD
BOOL
Load input for DATA
RESET
BOOL
Reset input
OUT
BOOL
Output