Appendix A—Technical Data and Specifications
212
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
Appendix A—Technical Data and Specifications
Communications Isolation Notes
The isolation between the Modbus Port and BCM electronics
is functional isolation only. All connections to the Modbus
terminal shall meet PELV requirements.
The isolation between the PROFIBUS Port and BCM
electronics is functional isolation only. All connections to
the PROFIBUS Port terminal shall meet PELV requirements.
The isolation between the Ethernet Port and BCM
electronics is functional isolation only. All connections to the
Ethernet Port terminal shall meet SELV/PELV requirements.
Table 70. Environmental Specifications
Table 71. Power Supply Specifications Summary
Notes
1
Fuse information—Recommend 1 A slow blow fuse for AC control power. Interrupting capability should be
greater than available branch current.
2
UL Listed Isolated Class 2/PELV Power Supply Rated Maximum 24 Vdc. Wiring must meet
PELV requirements.
3
Base Control Measurement User Int Communication Card.
Description
Specification
Temperature
–40 °C to 85 °C (–40 °F to 185 °F), non-operating
–40 °C to 60 °C (–40 °F to 140 °F), operating
Note: C445UM Monitoring User Interface LCD may not operate below –20 °C but
buttons will operate across the operating temperature range.
Operating Humidity
5–95% non-condensing
Altitude NEMA ICS1
2000 meters (6600 feet)
Shock IEC 60068-2-27
15 g any direction for 11 milliseconds, non-operating
Vibration IEC 60068-2-6
5 g non-operating and 3 g operating in any direction
Pollution Degree
3
Protection Degree
Internal Components: IP20
User Interface: IP54 & UL Type12
Cooling
Convection (natural)
Description
Specification
AC Control Power
1
Rated supply voltage (operating range):
110–120 Vac/60 Hz, (94–132 Vac)
220–240 Vac/50 Hz, (187–264 Vac)
Requirement of an external control power transformer when the product
is used above 150 Vac (220–240 Vac)
DC Control Power
2
Rated supply voltage (operating range):
24 Vdc Nominal (18–30 Vdc)
The common terminal of the 24 V power supply shall be earthed
Max. Power Consumption
3
8 W
AC Control Power Input Impulse
Withstand Voltage Uimp
See
Table 82
.