Appendix A—Technical Data and Specifications
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
215
Table 77. EMC Immunity
Table 78. Agency Certifications and Regulatory
Description
Specification
Surge
61000-4-5
Criteria B
2 kV Line to Earth
1 kV Line to Line
ESD
61000-4-2
Criteria B
8 kV air discharge
4 kV contact discharge
EFT
61000-4-4
Criteria B
Power Ports: 2 kV, 5 kHz, Direct Method
Signal Ports: 1 kV, 5 kHz, Clamp Method
Radiated Immunity
61000-4-3
Criteria A
10 V/m 80–2000 MHz, 80% amplitude modulation at 1 kHz
1 V/m 2000–2700 MHz, 80% amplitude modulation at 1 kHz
Conducted Immunity
61000-4-6
Criteria A
10 V/m, 0.15–80 MHz, 80% amplitude modulation a 1 kHz
Magnetic Field Immunity
61000-4-8
Criteria A
30 A/m, 50/60 Hz
Voltage Dips & Interruptions
61000-4-11
Criteria A
110 Vac 60 Hz, 220 Vac 50 Hz
0% rated voltage during 1/2 cycle
0% rated voltage during 1 cycle
70% rated voltage during 25/30 cycles
Voltage Interruptions
61000-4-11
Criteria A
110 Vac 60 Hz, 220 Vac 50 Hz
Interruption (0% rated voltage) during 250/300 cycles
Voltage Interruptions
61000-4-29
Criteria A
24 Vdc
Interruption (0% rated voltage) for 10 ms
Description
Specification
Agency Certifications
UL and CSA
UL 60947-4-1
CSA 22.2 #60947-4-1
CSA C22.2 NO. 0-10
Low Voltage directive (2006/95/EC)
IEC/EN 60947-4-1
IEC/EN 60947-5-1
EN 60947-8
EN 60079-7 (For increased safety method of protection of Ex e motor),
EMC directive (2004/108/EC),
Machine Directive (2006/42/EC),
IEC/EN 61000-4 level 3,
PROFIBUS/ODVA Conformance
Regulatory, self-declarations
Recast RoHS Directive/RoHS II (Restriction of the use of certain hazardous
substances in electrical and electronic equipment (recast) Directive 2011/65/EU)
WEEE Directive (Waste of Electrical and Electronic Equipment 2002/96/EC)
REACH Directive 2006/121/EC (Registration, Evaluation, Authorization, and
Restriction of Chemicals 1907/2006, 1. Compliance according with REACH article
67, and 2. The compliance of the duty to inform by the supplier according to REACH
article 31 and 33)
Life Cycle Assessment (LCA, reference ISO 14025)