Appendix D—Modbus Register Map
320
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
702
Control Interlocking Time
UINT16 RW NV
Default: 10
Range: 0 to 60000
Units: 10ms
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Time delay between “forward to reverse” or “reverse to forward”
direction change (in 0.1sec). Used in the Reverser operation mode.
703
Control Switching Time
UINT16 RW NV
Default: 10
Range: 0 to 60000
Units: 10ms
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Time delay between switching from fast to slow which allows the motor
time to slow down. (in 0.1sec). Used in operation modes with two speeds.
704
Network contactor delay
UINT16 RW NV
Default: 5
Range: 0 to 2000
Units: 10ms
Settling time for network contactor before RUN contactor engages (in
10ms). Used with the Star/Delta operation mode.
705
Max Star Winding Time
UINT16 RW NV
Default: 100
Range: 1 to 6000
Units: 100ms
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Parameters used in Star/Delta Operation Mode.The time after which the
controller will transition to delta wiring when “up to speed” is NOT
detected in the star winding
706
Enable HMCP Actuation
BOOL RW NV
Default: 0
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Enable HMCP Actuation Control when using the MCCB Feeder Operation
Mode. This allows the C445 Outputs 1 and 2 to turn the Circuit Breaker On
and Off.
707
HMCP Actuation Pulse
Width
UINT16 RW NV
Default: 500
Range: 100 to 60000
Units: ms
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
HMCP actuation pulse width or length of on-time to trigger motor
operator (in 1.0 ms).
708
Solenoid Open Delay Time
UINT16 RW NV
Default: 0
Units: 10ms
Config CRC
Admin Lock
USB Lock
Backup Mem
Delay time for solenoid valve to open (in 10ms). Used in Solenoid Valve
operation mode.