Appendix D—Modbus Register Map
364
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
1073
Auto Reset Types
BYTE RW NV
Array size: 4
Default: 0
Bitfield
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Select the protections that are to auto-reset if Auto Reset Enable is
enabled. Each protection type is a bit.
1075
Auto Reset Delay
UINT16 RW NV
Default: 180
Range: 0 to 3600
Units: seconds
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
The time delay following a fault before attempting to auto-reset that fault
condition.
1076
Reset on Powerup
BOOL RW NV
Default: FALSE
Config CRC
Admin Lock
USB Lock
Backup Mem
If enabled, perform a fault reset on power up.
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Bit
Description
Coil
0
Under voltage
17153
1
Over voltage
17154
2
Reserved
17155
3
Ground current fault
17156
4
Current phase loss
17157
5
Current unbalance
17158
6
Instantaneous over current
17159
7
Jam
17160
8
Power factor deviation
17161
9
Voltage phase loss
17162
10
Voltage unbalance
17163
11
Frequency deviation fast
17164
12
Frequency deviation slow
17165
13
Under current
17166
14
High power
17167
15
Low power
17168
16
Reserved
17169
17
Starts limit exceeded
17170
18
Overload
17171
19
Stall
17172
20
Phase rotation mismatch
17173
21
PTC
17174
22
Under voltage restart
17175
23
Peak demand
17176
24
HRGF pulse detection
17177