Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
355
1010
Jam Trip Delay
UINT16 RW NV
Default: 10
Range: 1 to 60
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
Jam Trip Delay is the time delay following the trip level being exceeded
until a trip occurs.
1011
Allowed Starts/hr
UINT16 RW NV
Default: 4
Range: 1 to 60
Config CRC
Admin Lock
USB Lock
Backup Mem
This protection works by limiting the number of starts per hour. Starting
the motor frequently can lead to motor windings overheating resulting in
a reduced life of the stator insulation. The user can choose a start limit
value as well as disabling the fault. Note that the start limit is only verified
when a start command is received.
1012
Instantaneous Overcurrent
Trip Level
UINT16 RW NV
Default: 400
Range: 50 to 400
Units: %
Config CRC
Admin Lock
USB Lock
Backup Mem
Instantaneous Overcurrent Trip Level, when exceeded and following the
Instantaneous Overcurrent Trip Delay time will generate a trip.
1013
Instantaneous Overcurrent
Alarm Level
UINT16 RW NV
Default: 400
Range: 50 to 400
Units: %
Config CRC
Admin Lock
USB Lock
Backup Mem
Instantaneous Overcurrent Alarm Level, when exceeded and following
the Alarm Delay Time in the Protections/General category, will generate a
warning.
1014
Instantaneous Overcurrent
Start Delay
UINT16 RW NV
Default: 0
Range: 0 to 180
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
Instantaneous Overcurrent Start Delay is a delay at power up to inhibit
raising this trip condition until this time expires. If the condition is no
longer present when this time expires, no trip will occur.
1015
Instantaneous Overcurrent
Trip Delay
UINT16 RW NV
Default: 2000
Range: 1 to 2000
Units: ms
Config CRC
Admin Lock
USB Lock
Backup Mem
Instantaneous Overcurrent Trip Delay is the time delay following the trip
level being exceeded before a trip occurs.
1016
I Phase Loss Trip Level
Percent
INTERNAL
UINT8 RO
Default: 60
Units: %
I Phase Loss Trip Level Percent
1017
I Phase Loss Debounce
INTERNAL
UINT16 RO
Default: 2
Units: seconds
I Phase Loss Debounce
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description