Appendix C—Optional Communication Cards
256
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
36
4
Warning Reason
STATUS_WARNING_BITS, continued
0x0001 0000 - Reserved
0x0002 0000 - exceeds starts limit
0x0004 0000 - overload
0x0008 0000 - stall
0x0010 0000 - phase rotation mismatch
0x0020 0000 - PTC
0x0040 0000 - under voltage restart
0x0080 0000 - peak demand
0x0100 0000 - HRGF pulse detection
40
2
Thermal Pile
Percentage
OVLD_THERMAL_MEM_PERCENT:
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip (%)
42
2
Digital Inputs
Bits 0-7 = Inputs for the first digital input card
Bits 8-15 = Inputs for the second digital input card
44
2
Digital Inputs
Bits 0-7 = Inputs for the third digital input card
Bits 8-15 = Inputs for the fourth digital input card
46
12
Analog Inputs
6 Input words of data for analog inputs and status word(s)
Input Instance 119 (0x77): Full Monitoring with Extended Analog and Digital Inputs
Length = 70 Bytes
Byte
Offset
Size
(bytes)
Name
Description
0
2
Device Status
C445_DEVICE_STATUS:
Device Bit Array
Bit 0: Faulted/Tripped
Bit 1: Warning
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Running1
Bit 9: Running2
Bit 10: Remote or CtrlFromNet
Bit 11: Output #3
Bit 12: Reserved
Bit 13: Inhibited
Bit 14: Ready
Bit 15: AtRef or Up-To-Speed
2
2
Current L1
MOTOR_I_A_SCALED:
Phase A (L1) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
4
2
Current L2
MOTOR_I_B_SCALED:
Phase B (L2) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
Input Instance 118 (0x76): Full Monitoring with Analog and Digital Inputs, continued
Length = 58 Bytes
Byte
Offset
Size
(bytes)
Name
Description