Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
345
771
Stop LED Color
UINT8 RW NV
Default: 0
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI Stop Button LED Color
772
Auto LED Color
UINT8 RW NV
Default: 2
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI Auto Button LED Color
773
Start Button Debounce
UINT16 RW NV
Default: 50
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI start button debounce time in milliseconds.
774
Stop Button Debounce
UINT16 RW NV
Default: 50
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI stop button debounce time in milliseconds.
775
Auto Button Debounce
UINT16 RW NV
Default: 50
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI auto button debounce time in milliseconds.
776
Reset Button Debounce
UINT16 RW NV
Default: 250
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI reset button debounce time in milliseconds.
777
Enable Fieldwire Inputs
BYTE RW NV
Default: 0x0F
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
BCM Fieldwire Control Inputs Enable
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Value
Description
0
Green
1
Red
2
Amber
3
White
255
Off
Value
Description
2
Amber
3
White
255
Off
Bit
Description
Coil
0
Input1 (I1)
12417
1
Input1 (I2)
12418
2
Input1 (I3)
12419
3
Input1 (I4)
12420