Chapter 5—System Configuration and Operation
68
Power Xpert C445 Global Motor Management Relay
MN042003EN—January 2019
www.eaton.com
Figure 62. 120 Vac Inputs and 120/230 Vac Outputs/C445 Power
Notes:
1.
The inputs on the Base Control Module are only used by
this Operation Mode if Fieldwire is selected for one of
the control sources. If Fieldwire is not the Local or
Remote control source, all 4 inputs may be used as
general purpose inputs.
2.
Input 2 and Outputs 2 and 3 may be used as general
purpose I/O for this operation mode.
3.
If Fieldwire is the Local control source, Input 3 is the
Remote input. When power is applied to Input 3, the
C445 will be in Remote mode.
4.
If Fieldwire is the Remote control source and 2-wire
control (default) is selected, Input 3 is unused by this
operation mode.
5.
Fusing: Although C445 product listings do not require
fusing on the high impedance line voltage measurement
inputs, it may be necessary to provide overcurrent
protection of the supply leads in accordance with
applicable final installation specific local, state and
national electrical codes.
CH1
T1
T2
V1
V2
V3
C445M...
I1
I2
C445BA-SA...
CH1
CH2
CH1
C445U…
I3
I4
IC
Q1
Q1
Q2
Q2
Q3
C
Q3
C
D0
D1
CH2
PTC
MOTOR
3~
L2
L3
PE
L1
Optional Modbus
Q11
Q1
PE
N
L
(+) Us
(-) Us
120/240 VAC
IC
IC
FB1
FERRITE
RESET
REMOTE
TEST
TRIP
Q11
RUN
(+) Uc
(-) Uc
120 VAC