714
Local/Remote PowerUp
Behavior
UINT8 RW NV
Default: 2
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
Select the Local/Remote mode the Base Control Module will power up in.
Selections: 0: Local control is active control on power up, 1: Remote
control is active control on power up, 2: Hold last control state on
power up.
715
Q1 Function Select
UINT16 RW NV
Default: 54
Enum
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Output Function Select for General Purpose Output 1. Available when this
output is not used by the Operation Mode. Default = none, If used by the
Application Mode = Reserved. A soft reset is required after modifying this
parameter.
Table 128. C445 Modbus Register Map, continued
Register
Name
Attribute
Description
Value
Description
0
Local control is active control on power-up
1
Remote control is active control on power-up
2
Hold last control state on power-up
Value
Description
0
None
1
Fault Reason Type - Load fault (Power based)
2
Fault Reason Type - Supply fault (Voltage based)
3
Fault Reason Type - Motor fault (Current based)
4
Tripped Status Bits - PTC
5
Tripped Status Bits - Phase rotation mismatch
6
Tripped Status Bits - Stall
7
Tripped Status Bits - Overload
8
Tripped Status Bits - Starts limit exceeded
9
Tripped Status Bits - Low power
10
Tripped Status Bits - High power
11
Tripped Status Bits - Under current
12
Tripped Status Bits - Frequency deviation slow
13
Tripped Status Bits - Frequency deviation fast
14
Tripped Status Bits - Voltage unbalance
15
Tripped Status Bits - Voltage phase loss
16
Tripped Status Bits - Power factor deviation
17
Tripped Status Bits - Jam
18
Tripped Status Bits - Instantaneous over current
19
Tripped Status Bits - Current unbalance
20
Tripped Status Bits - Current phase loss
21
Tripped Status Bits - Ground fault
22
Motor Control Status - Motor at speed
23
Motor Control Status - Ready
24
Motor Control Status - Inhibited
25
Motor Control Status - Warning
26
Motor Control Status - Faulted
27
Motor Control Status - Remote enabled
28
Motor Control Status - Running 2
29
Motor Control Status - Running 1